Pre-acting device

ZSFY

Retail price

Market price


Weight

kg

Quantity
-
+

Stock

隐藏域元素占位

Classification:

Key words:

Pre-acting device

  • Product Description
    • Commodity name: Pre-acting device
    • Commodity ID: ZSFY

    1. model preparation:

    Example: ZSFY150-1.6 indicates a pre-acting device with a nominal diameter of 150mm and a rated working pressure of 1.6MPa

     

    2. executive standard: GB5135.14-2011 "automatic sprinkler system part 14: pre-action device"

     

    3. technical parameters:

     

    Model specifications

    Nominal diameter (mm)

    Rated working pressure (MPa)

    Working pressure range (MPa)

    Alarm port pressure (MPa)

    Inflation pressure on system side (MPa)

    Alarm air pressure (MPa)

    Environmental conditions for system use

    Upper Limit

    lower limit

    ZSFY100-1.6

    100

    1.6

    0.14~1.6

    4-70

    0.03~0.05

    0.06

    0.02

    <4 ℃ or> 70 ℃

    ZSFY150-1.6

    150

    ZSFY200-1.6

    200

     

    4. applicable places: commonly used in places where pipeline leakage or accidental spraying are not allowed; at the same time, it can also replace the dry automatic water spray alarm system for occasions where the wet automatic water spray alarm system is not available due to cold or high temperature. Such as senior hotels, hospitals, important office buildings, large shopping malls, libraries and other places.

1. model preparation:

Example: ZSFY150-1.6 indicates a pre-acting device with a nominal diameter of 150mm and a rated working pressure of 1.6MPa

 

2. executive standard: GB5135.14-2011 "automatic sprinkler system part 14: pre-action device"

 

3. technical parameters:

 

Model specifications

Nominal diameter (mm)

Rated working pressure (MPa)

Working pressure range (MPa)

Alarm port pressure (MPa)

Inflation pressure on system side (MPa)

Alarm air pressure (MPa)

Environmental conditions for system use

Upper Limit

lower limit

ZSFY100-1.6

100

1.6

0.14~1.6

4-70

0.03~0.05

0.06

0.02

<4 ℃ or> 70 ℃

ZSFY150-1.6

150

ZSFY200-1.6

200

 

4. applicable places: commonly used in places where pipeline leakage or accidental spraying are not allowed; at the same time, it can also replace the dry automatic water spray alarm system for occasions where the wet automatic water spray alarm system is not available due to cold or high temperature. Such as senior hotels, hospitals, important office buildings, large shopping malls, libraries and other places.