Mechanical pump-in proportional mixing device

  • Product Description
    • Commodity name: PHP mechanical pump-in proportional mixing device

    Product Introduction

    The mechanical pump-in proportional mixing device is a flow-balanced proportional mixing device, which is composed of a water turbine (non-drainage type), a foam liquid pump, a coupling, a valve, a piping system, a PLC control cabinet, a foam liquid storage tank and a base. The unit consists of two key components: a water turbine and a foam pump. The fire water flowing in the pipeline is used as the driving force, and the foam liquid pump is driven by the water turbine to extract the foam liquid in the atmospheric pressure tank and pump it into the main fire pipeline. Through the matching of the internal structural parameters of the water turbine and the foam liquid pump, the flow rate of water and the flow rate of foam liquid are balanced, and the proportional mixing is realized. When the three-way valve on the pipeline system closes the suction port, the foam pump will automatically clean.
    It is mainly suitable for large, medium and small foam fire fighting systems in substations, underground parking lots, petrochemicals, ports, oil depots, airports (depots), offshore platforms and other places.

     

    Working principle

    The fire water flows through the water turbine. The water turbine rotates and drives the plunger pump. The plunger pump sucks the foam liquid, pressurizes it and injects it into the outlet of the water turbine, and mixes it with water to form a foam mixture. The amount of foam liquid is proportional to the flow rate and is independent of the pressure change, so that a stable mixing ratio can be guaranteed under the condition of pressure change.
    Because water needs to consume a certain amount of energy to do work, the fire water flowing through the hydraulic motor will have a certain pressure loss. The pump-in proportional mixing device produced by our company has a pressure loss of fire water within 0.15MPa under the working pressure of 1.6MPa.

    Working Schematic Diagram

    1. Fire water supply 2, water turbine (non-drain type) 3, plunger pump 4, coupling 5, foam liquid supply 6, bottom filter 7, suction pipe 8, three-way ball valve (flushing/suction) 9, flushing pipe 10, fire water pipe 11, check valve 12, injection pipe 13, exhaust pipe 14, fire water filter 15, flushing pipe 16, flushing pipe filter 17, suction pipe swing check valve 18, pressure release valve 19, tee (mixing/return) 20, bottom valve 21, suction pipe exhaust

     

    Product advantages

    1. It is suitable for all foam fire extinguishing systems and can replace pressure proportional mixing device and balanced proportional mixing device with accurate mixing ratio.
    2. Easy to install, hydraulic drive, no additional power required. Compact, light weight, no pressure vessel required.
    3. Simple to use, simple mechanical mixing, wide flow range, wide pressure range, no correction required.
    4. Economical and efficient, simple maintenance, simple regular testing, low maintenance cost during the use period.

     

    Technical parameters

    Model specifications

    Flow range

    (L/S)

    Working pressure range

    (MPa)

    mixing ratio

    (%)

    Supervisor caliber

    A(mm)

    Foam liquid inlet

    C(mm)

    Return port

    B(mm)

    Pressure relief port

    D(mm)

    L(mm)

    H(mm)

    W(mm)

    X(mm)

    PHP8

    1~8

    06~1.2 or 0.6~1.6

    3% or 6%

    DN50

    1〞

    1/2〞

    1/2〞

    700

    250

    400

    350

    PHP16

    3~16.6

    DN65

    1〞

    1/2〞

    1/2〞

    850

    260

    450

    350

    PHP25

    3~26.5

    DN100

    11/2〞

    1〞

    3/4〞

    990

    350

    500

    400

    PHP40

    4.2~40

    DN100

    2〞

    1〞

    3/4〞

    1200

    350

    500

    450

    PHP66

    8~66.5

    DN150

    2 1/2〞

    1〞

    3/4〞

    1250

    400

    600

    500

    PHP100

    8~100

    DN200

    21/2〞

    11/2〞

    1〞

    1450

    550

    600

    550

    PHP135

    8~135

    DN250

    21/2〞

    11/2〞

    DN40

    1750

    1000

    1000

    700

    PHP170

    18~170

    DN300

    21/2〞

    2〞

    DN50

    1800

    1050

    1000

    700

    PHP250

    20~250

    DN350

    DN100

    DN65

    DN65

    2800

    1200

    1600

    950

    PHP335

    30~335

    DN400

    DN125

    DN65

    DN65

    2800

    1180

    1600

    950

     

    System Control

    The mechanical pump-in proportional mixing device adopts PLC automatic control system, which can well solve the problem that when a fire occurs in the case of unattended operation, the opening and closing of the inlet valve and the inlet valve are controlled according to the set program at the first time to start or close the device, and the state signal of corresponding action is displayed on the control cabinet at the same time. Can accept the automatic fire alarm signal of the central control and implement automatic fire extinguishing accordingly.
    The control system has two modes: automatic control and on-site manual control.

    1) Automatic control

    When the control cabinet is in the automatic control mode, the PLC control system receives the fire alarm signal or manually confirms the fire according to the information of the fire alarm system and manually opens the start button of the fire control room device. After receiving the instruction, the device control system automatically opens the main system fire water inlet valve (normally closed) and foam liquid inlet valve (normally closed), and detects whether the foam liquid pump is normally started through the main foam liquid pump outlet pressure transmitter, when the outlet pressure of the foam liquid pump reaches the set value (≥ 0.6MPa), it means that the pipe network pressure has been established and the main system has been successfully started; if the pump outlet still does not reach the set value 30s (adjustable) after the foam liquid pump is started, the device system will give an alarm, the main system will stop and automatically switch to the standby system.
    When any control equipment of the main system in the unit fails, alarm will be given and the standby system will be started in turn. The alarm signal can be uploaded to the fire control room fire linkage controller, in the fire control room alarm.

    2) On-site manual control:

    In case of fire, directly start the device into operation by operating the button on the control cabinet of the device. The operation of the device is automatically controlled by the control cabinet program. The control cabinet program control process is the same as above. If the electric valve fails to start, it can also be opened directly by mechanical manual. After the fire is put out, close all electric devices on site through the button on the field control cabinet.

     

    Installation of device

    1. Check whether the skid of the mechanical pump-in proportional mixing device is damaged during transportation.

    2. Use a lifting tool to place the mixing device skid on the equipment installation foundation and fix it with anchor bolts.

    3. Install the foam tank on its foundation and fix it with anchor bolts. After the foam tank is fixed, install the accessories of the foam tank such as liquid level gauge and breathing valve to the corresponding position of the foam tank.

    4. Correctly connect the fire water inlet on the skid block and the foam mixed solution outlet with the main pipe, and correctly connect the foam stock solution inlet and the foam stock solution return port with the foam stock solution outlet and the foam stock solution return port on the foam tank.

    5. After the equipment is installed, check whether the flange connecting bolts of the skid block pipeline are loose during transportation. If there is any looseness, please tighten it again to prevent leakage.

     

    Inspection and preparation before device start-up

    1. Foam tank inspection: open the manhole cover of the foam tank and check whether there is dust, dirt and stains in the foam tank. If so, rinse the foam tank with clean water and let it dry.

    2. Foam liquid filling: Before filling foam liquid, please check whether all valves of the foam tank are closed to prevent leakage and loss of foam liquid. It is recommended to use a liquid filling pump to pump into the foam tank from the liquid filling port of the tank. If there is no liquid filling pump, it can only be injected from the manhole of the tank top (it is better not to pour from the manhole, so a large amount of foam will be generated when filling the foam liquid, which is easy to overflow). When excessive foam is generated during the filling of foam liquid, please stop filling and continue filling after the foam disappears to prevent overflow.

    3. Check the switch status of each valve of the skid.

    4. Start the fire pump to supply water to the main pipe of the skid block. At this time, open the fire water inlet valve and the foam liquid inlet valve, and the system will run in the working state.

     

    Flushing after unit operation

    1. After the operation of the foam system is completed, the skid pipe, foam pump and valve shall be flushed with clean water.

    2. When flushing the system, the valves of the system shall be adjusted to the flushing position according to the requirements of the system valve switch state table.

    3. When the system valve is adjusted to the flushing state, the flushing time is about 2 to 5 minutes, and the discharged water no longer contains foam.

    4. After flushing, the valves of the system must be restored to the standby state and ready to run again at any time.

Product Introduction

The mechanical pump-in proportional mixing device is a flow-balanced proportional mixing device, which is composed of a water turbine (non-drainage type), a foam liquid pump, a coupling, a valve, a piping system, a PLC control cabinet, a foam liquid storage tank and a base. The unit consists of two key components: a water turbine and a foam pump. The fire water flowing in the pipeline is used as the driving force, and the foam liquid pump is driven by the water turbine to extract the foam liquid in the atmospheric pressure tank and pump it into the main fire pipeline. Through the matching of the internal structural parameters of the water turbine and the foam liquid pump, the flow rate of water and the flow rate of foam liquid are balanced, and the proportional mixing is realized. When the three-way valve on the pipeline system closes the suction port, the foam pump will automatically clean.
It is mainly suitable for large, medium and small foam fire fighting systems in substations, underground parking lots, petrochemicals, ports, oil depots, airports (depots), offshore platforms and other places.

 

Working principle

The fire water flows through the water turbine. The water turbine rotates and drives the plunger pump. The plunger pump sucks the foam liquid, pressurizes it and injects it into the outlet of the water turbine, and mixes it with water to form a foam mixture. The amount of foam liquid is proportional to the flow rate and is independent of the pressure change, so that a stable mixing ratio can be guaranteed under the condition of pressure change.
Because water needs to consume a certain amount of energy to do work, the fire water flowing through the hydraulic motor will have a certain pressure loss. The pump-in proportional mixing device produced by our company has a pressure loss of fire water within 0.15MPa under the working pressure of 1.6MPa.

Working Schematic Diagram

1. Fire water supply 2, water turbine (non-drain type) 3, plunger pump 4, coupling 5, foam liquid supply 6, bottom filter 7, suction pipe 8, three-way ball valve (flushing/suction) 9, flushing pipe 10, fire water pipe 11, check valve 12, injection pipe 13, exhaust pipe 14, fire water filter 15, flushing pipe 16, flushing pipe filter 17, suction pipe swing check valve 18, pressure release valve 19, tee (mixing/return) 20, bottom valve 21, suction pipe exhaust

 

Product advantages

1. It is suitable for all foam fire extinguishing systems and can replace pressure proportional mixing device and balanced proportional mixing device with accurate mixing ratio.
2. Easy to install, hydraulic drive, no additional power required. Compact, light weight, no pressure vessel required.
3. Simple to use, simple mechanical mixing, wide flow range, wide pressure range, no correction required.
4. Economical and efficient, simple maintenance, simple regular testing, low maintenance cost during the use period.

 

Technical parameters

Model specifications

Flow range

(L/S)

Working pressure range

(MPa)

mixing ratio

(%)

Supervisor caliber

A(mm)

Foam liquid inlet

C(mm)

Return port

B(mm)

Pressure relief port

D(mm)

L(mm)

H(mm)

W(mm)

X(mm)

PHP8

1~8

06~1.2 or 0.6~1.6

3% or 6%

DN50

1〞

1/2〞

1/2〞

700

250

400

350

PHP16

3~16.6

DN65

1〞

1/2〞

1/2〞

850

260

450

350

PHP25

3~26.5

DN100

11/2〞

1〞

3/4〞

990

350

500

400

PHP40

4.2~40

DN100

2〞

1〞

3/4〞

1200

350

500

450

PHP66

8~66.5

DN150

2 1/2〞

1〞

3/4〞

1250

400

600

500

PHP100

8~100

DN200

21/2〞

11/2〞

1〞

1450

550

600

550

PHP135

8~135

DN250

21/2〞

11/2〞

DN40

1750

1000

1000

700

PHP170

18~170

DN300

21/2〞

2〞

DN50

1800

1050

1000

700

PHP250

20~250

DN350

DN100

DN65

DN65

2800

1200

1600

950

PHP335

30~335

DN400

DN125

DN65

DN65

2800

1180

1600

950

 

System Control

The mechanical pump-in proportional mixing device adopts PLC automatic control system, which can well solve the problem that when a fire occurs in the case of unattended operation, the opening and closing of the inlet valve and the inlet valve are controlled according to the set program at the first time to start or close the device, and the state signal of corresponding action is displayed on the control cabinet at the same time. Can accept the automatic fire alarm signal of the central control and implement automatic fire extinguishing accordingly.
The control system has two modes: automatic control and on-site manual control.

1) Automatic control

When the control cabinet is in the automatic control mode, the PLC control system receives the fire alarm signal or manually confirms the fire according to the information of the fire alarm system and manually opens the start button of the fire control room device. After receiving the instruction, the device control system automatically opens the main system fire water inlet valve (normally closed) and foam liquid inlet valve (normally closed), and detects whether the foam liquid pump is normally started through the main foam liquid pump outlet pressure transmitter, when the outlet pressure of the foam liquid pump reaches the set value (≥ 0.6MPa), it means that the pipe network pressure has been established and the main system has been successfully started; if the pump outlet still does not reach the set value 30s (adjustable) after the foam liquid pump is started, the device system will give an alarm, the main system will stop and automatically switch to the standby system.
When any control equipment of the main system in the unit fails, alarm will be given and the standby system will be started in turn. The alarm signal can be uploaded to the fire control room fire linkage controller, in the fire control room alarm.

2) On-site manual control:

In case of fire, directly start the device into operation by operating the button on the control cabinet of the device. The operation of the device is automatically controlled by the control cabinet program. The control cabinet program control process is the same as above. If the electric valve fails to start, it can also be opened directly by mechanical manual. After the fire is put out, close all electric devices on site through the button on the field control cabinet.

 

Installation of device

1. Check whether the skid of the mechanical pump-in proportional mixing device is damaged during transportation.

2. Use a lifting tool to place the mixing device skid on the equipment installation foundation and fix it with anchor bolts.

3. Install the foam tank on its foundation and fix it with anchor bolts. After the foam tank is fixed, install the accessories of the foam tank such as liquid level gauge and breathing valve to the corresponding position of the foam tank.

4. Correctly connect the fire water inlet on the skid block and the foam mixed solution outlet with the main pipe, and correctly connect the foam stock solution inlet and the foam stock solution return port with the foam stock solution outlet and the foam stock solution return port on the foam tank.

5. After the equipment is installed, check whether the flange connecting bolts of the skid block pipeline are loose during transportation. If there is any looseness, please tighten it again to prevent leakage.

 

Inspection and preparation before device start-up

1. Foam tank inspection: open the manhole cover of the foam tank and check whether there is dust, dirt and stains in the foam tank. If so, rinse the foam tank with clean water and let it dry.

2. Foam liquid filling: Before filling foam liquid, please check whether all valves of the foam tank are closed to prevent leakage and loss of foam liquid. It is recommended to use a liquid filling pump to pump into the foam tank from the liquid filling port of the tank. If there is no liquid filling pump, it can only be injected from the manhole of the tank top (it is better not to pour from the manhole, so a large amount of foam will be generated when filling the foam liquid, which is easy to overflow). When excessive foam is generated during the filling of foam liquid, please stop filling and continue filling after the foam disappears to prevent overflow.

3. Check the switch status of each valve of the skid.

4. Start the fire pump to supply water to the main pipe of the skid block. At this time, open the fire water inlet valve and the foam liquid inlet valve, and the system will run in the working state.

 

Flushing after unit operation

1. After the operation of the foam system is completed, the skid pipe, foam pump and valve shall be flushed with clean water.

2. When flushing the system, the valves of the system shall be adjusted to the flushing position according to the requirements of the system valve switch state table.

3. When the system valve is adjusted to the flushing state, the flushing time is about 2 to 5 minutes, and the discharged water no longer contains foam.

4. After flushing, the valves of the system must be restored to the standby state and ready to run again at any time.